Description
Luxpower Inverter BXP6000-10Kw :
Specification
Battery Module :
Battery Power (kWh): 5.12
Rated Voltage (V): 51.2
Rated Capacity (Ah): 100
Battery Type: Lithium-ion
Max. Parellel (Default): 2PCS
Max. Discharging Current (A): 100
Max. Charging Current (A): 100
Dimension (W*H*D) (mm): 580x434x165
Net Weight: 54Kg
Standard: UN38.3,CE
Inverter Module: BXP6000
Input (PV DC)
Max. PV Array Power (W): 8000(4000/4000)
Rated pV Input Voltage (V): 320
Number of Independent MPPT Inputs: 2
PV Input Voltage Range (V): 100-480
MPPT Voltage Range (V) : 120-385
Start-up Voltage (V): 100
Max. PV Input Current per MPPT (A): 17/17
Max. Py Short-circuit Current per MPPT (A): 25/25
Max. PV Charging Current (A): 125
Battery Input
Battery Volatge (V): 38.4`60
Max. Charging/Discharging Current (A): 125/140
Max. Charging/Discharging Power (W): 6000
Protection: Over Voltage, under Voltage,Over Current,Short Circuit, Over Temperature
UPS output @off-grid
Output Voltage Waveform: Pure sine wave
Output Voltage Regulation (V): 208/220/230/240+-5%
Output Frequency (Hz) : 50/60
Rated Output Power (W): 6000
Rated Output Current (A): 26.5
Peak Efficiency : 93%
Overload Protection: 5s@>-150% overload;10s@110%¬150% overload
Surge Power: 2*Pn,5s
Parallel Quantity: 16PCS
AC Input
Nominal Input Voltage (V): 230
Nominal Input Frequency: (Hz)50/60(Auto detection)
Max. AC Input Current (A): 39.5
Max. AC Input Power (W): 9000
Max. AC Charging Current (A): 125
AC Output :Gird
Rated AC Output Current (A): 26.5
Rated AC Output Power (W): 6000
Rated AC Current of Bypass Relays (A): 60
Switching Time; Typical<10ms @ Single; <30ms @ Parallel
Generator Input
Rated GEN Voltage (V) 220/230/240
Rated GEN Frequency (Hz) 50/60
Rated GEN Input Current (A) 32
Rated GEN Input Power (W)7370
Rated GEN Current of Bypass Relays (A)60